10
PrevaLED
®
Core Z3 LED modules | Electrical considerations
3.3 Wiring
The input clamps used in the PrevaLED
®
Core Z3 can hand-
le solid wires with a cross-section of 0.5–1.0 mm
2
(AWG 21-17).
Example: H05V-U 1x 0.5 mm2
Please note:
The connector is designed for three “poke-in” and
release cycles.
The installation of LED modules needs to be carried out
in compliance with all applicable electrical and safety
standards. Only qualifi ed personnel should be allowed to
perform installations.
If you cannot use solid wires, you can use stranded wires
with a diameter of 0.5 to 0.75 mm and tin-coat the wire
ends before inserting them into the connection clamp.
For wires with
1 mm
2
(AWG17):
5.5 mm
For wires with
0.5-0.823 mm
2
(AWG21–18):
5.3 +- 0.2 mm
Wire preparation